Power Supply


VF8004 Power Supply- 8 Amps 

VES LLC VF8004 is an 8 Amp, 24VDC, filtered and regulated, supervised remote power supply/charger used for supervision and expanded power driving capability for Fire Alarm Notification Appliance Circuits. The VF8004 may be connected to any 12V or 24V (FWR or DC) Fire Alarm Control Panel (FACP) by using a Notification Appliance Circuit (NAC) or a “Dry Contact”. Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support system accessories. This unit provides filtered and regulated 24VDC, 8 Amp up to four (4) Class “B”, two (2) Class “A”, or two (2) Class “B” and one (1) Class “A” Notification Appliance Circuits. With the optional plug-in module the unit supports (4) Class “A” Notification Appliance Circuits.

Additionally, an auxiliary power output of 3.5 Amps (disconnected upon AC power loss or an alarm condition) or 200 mAmps (constant) is provided, which can be manually reset. Two FACP NAC circuits or two “Dry” contact initiating circuits can be connected to the VF8004 inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs.

Each output is rated at 3.0 Amps (Class “B”) or (Class “A”) and can be programmed to generate a steady or Code 3 Temporal Horn sound and a strobe output under alarm condition. Total load for the PS-24-8MC NAC circuits must not exceed 8.0 Amps.

The VF8004 is UL Listed under UL Standard 864, 9th Edition to be used with any 24 volt Listed Regulated notification appliances that use the supported protocol.

STANDARD FEATURES (VF1000)

Inputs
120VAC, 50/60Hz, 5.0 Amps Operating Power in Alarm
24VDC Battery Backup Connection
Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA) FWR or DC
Two (2) “Dry” Contact initiating Circuits
Accepts two (2) Class “A” or two (2) Class “B” circuit inputs
Built in battery charger

Outputs
NAC outputs are 24VDC, 3.0 Amps each, power limited
8 Amps total alarm current
Capable of four (4), Class “B” circuits
Capable of two (2) Class “A” circuits
Capable of four (4) Class “A” circuits with optional PS-4CA module
Capable of one (1) Class “A” circuit and two (2) Class “B” circuits
Temporal (Code 3) or constant voltage output
Built-in synchronization mode that can be fed to any or all of the output circuits
Input and output can be synchronized with “IN>OUT SYNC” mode
(SM, DSM or 2nd PS-24-8MC is required)
Audible silence capability
Filtered and electronically regulated output
3.5 Amp auxiliary power limited output with reset capability. (Removed upon AC
loss or alarm). Automatic reset 30 seconds after AC power returns or the alarm
condition is over) or 200 mAmps auxiliary power limited output which remains
on during AC loss or an alarm condition