VF6011 CZM: Conventional Zone Module
|
|
The Conventional Zone Module (CZM) is designed for use on the eLAN analog addressable FACP. Up to 127 devices can be placed on a single SLC loop. The device address is uniquely stored on an onboard EEPROM. The module allows the panel to interface and monitor dry contacts such as two-wire conventional detectors or pull stations. Each CZM is addressed through the panel and transmits the status of one zone of devices (25 maximum per zone) back to the panel. The module has a single bi-colored LED to indicate device status. It fits into a standard 4" square or double gang electrical back box.
|
CZM STANDARD FEATURES
• Provides an address point for a zone of up to 25 conventional smoke detectors
• Blinks green when polled. Latched on red (controlled by panel) when activated
• Device address can also be programmed with a handheld programmer. Device ...Address- ranges from 1 to 127
• Compatible with Class B (Style B) and Class A (Style D) wiring
• Auxiliary power source provides power for the zone of detectors
|
|
Down Loads
VF6011 CZM: Conventional Zone Module
|
|
VF6007 DIMM: Dual Monitor Module
|
|
The Dual Monitor Module (DIMM) is designed for use on the eLAN analog addressable FACP. It provides two independent contact monitoring circuits while only utilizing one address on the SLC loop. Up to 127 devices can be placed on a single SLC loop. The device address is uniquely stored on an onboard EEPROM. The module can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contact fire alarm and supervisory devices. The interrupt driven Digital Communication Protocol (DCP) combines maximum communication reliability and fast response to emergency conditions. The module has a single bi-colored LED to indicate device status. It fits into a standard 4" square or double gang
|
VF6007 DIMM STANDARD FEATURES
• Dual input contact monitor
• Fast, reliable contact monitoring utilizing the DCP
...(Digital Communications Protocol)
• 127 devices can be used per DCP loop
• Bi-colored indicating LED provides module status
• Operates on Class A or Class B SLC loop
• Accepts up to 14 AWG wire
• Mounts to 4" square gang box
|
|
Down Loads
VF6007 DIMM: Conventional Zone Module
|
|
VF6001 & VF6002 FRCM: Fast Response Contact Module
|
|
VES LLC’ Fast Response Contact Monitoring Modules are designed to be used with pull stations, water flow switches, and other applications requiring the monitoring of dry contact alarm initiating devices. The interrupt driven Digital Communications Protocol (DCP) combines maximum communication reliability and fast response to emergency conditions. Two different mounting configurations are provided to meet a wide range of applications. The contact monitoring module does not require a separate 24 VDC power source.
The VF6001 is a small package design and is suitable for mounting in a small junction box behind a pull station or other monitored device. See VF3001 and VF3002 for single and double action addressable pull stations.
The VF6002 is mounted to a cover plate for a 4" square or double gang junction box. It comes with a visible bi-colored indicating LED to provide module status.
|
|
FRCME-P: FAST RESPONSE CONTACT MODULE STANDARD FEATURES
• Single input contact monitor
• Fast, reliable contact monitoring utilizing the DCP
...(Digital Communications Protocol)
• Two different mounting configurations
• 127 devices can be used per DCP loop
• Can be programmed to monitor Normally Open (NO) or
...Normally closed (NC) contacts
• Operates on Class A or Class B SLC loop
• UL listed UL 864
|
|
FRCME-S: FAST RESPONSE CONTACT MODULE STANDARD FEATURES
• Single input contact monitor
• Fast, reliable contact monitoring utilizing the DCP
...(Digital Communications Protocol)
• 127 devices can be used per DCP loop
• Two different mounting configurations
• Can be programmed to monitor Normally Open (NO) or
...Normally closed (NC) contacts
• Operates on Class A or Class B SLC loop
• Accepts up to 14 AWG wire
• UL listed UL 864
|
|
Down Loads
VF6001 & VF6002 Fast Response Contact Modules |
|
VF6004 SOM: Supervised Output Module
|
|
The Supervised Output Module (SOM) has been designed to provide application flexibility and quick response to emergency conditions. Flexibility is provided by a wide range of operating modes, including supporting multi-zone operations, and/or functions, up to 16 different modulation patterns and multi-state programming. The operating parameters for the SOM are maintained by the module and do not require individual communication with the control system during emergency conditions to operate. The control panel simply broadcasts system conditions on the Signaling Line Circuit (SLC) and the SOMs respond based upon the custom configuration. Each SOM provides a Class B Individual Circuit rated for 2.0 Amp @ 30 VDC. Each SOM also requires a 24 Volt power source in addition to the SLC connection.
|
|
VF6004 SOM SUPERVISED OUTPUT MODULE STANDARD FEATURES
• Flexible application
• Quick response to emergency conditions
• Operation parameters are maintained by the module, and individual
...communication with the control system during emergency conditions
...is not required
• Contacts are rated 2.0 Amps @ 30 VDC
• Programming is highly flexible, providing 16 priority states plus zoning capability.
|
|
|
|
|
VF6005: Dual Relay Module
|
Each VF6005 module provides independent control of two Form C contacts while utilizing one SLC (Signaling Line Circuit) address. Up to 254 addressed outputs can be attached to each SLC loop. This dual relay module has a highly configurable programming algorithm that allows the user to setup groups of devices (zoning) for simultaneous operation of multiple VF6005 modules. Each module has 16 priority states that are programmed to generate modulation patterns. The operating parameters are maintained by the module and do not require individual communication with the control panel during the emergency condition to operate. The control panel broadcasts the common on the SLC loop and the VF6005 modules do the rest based on their custom configuration. Since mechanically latching relays are used within this dual relay module, a separate power source is not required.
|
VF6005 DUAL RELAY MODULE STANDARD FEATURES
• Provides two independently configurable Form C contacts per address
• Contacts are rated 2.0 Amps @ 30 VDC, or 1.0 Amp @ 125 VAC
• Up to 254 addressed outputs can be attached to each SLC loop
• Visible bi-colored LED is software-controlled and can be programmed to blink red or green when polled. LED can be latched when activated.
• Programming is highly flexible, providing 16 priority states plus zoning capability
|
|
Down Loads
VF6005 Dual Relay Module |
|
VF6003: Short Circuit Isolator
|
|
The Supervised Output Module (SOM) has been designed to provide application flexibility and quick response to emergency conditions. Flexibility is provided by a wide range of operating modes, including supporting multi-zone operations, and/or functions, up to 16 different modulation patterns and multi-state programming. The operating parameters for the SOM are maintained by the module and do not require individual communication with the control system during emergency conditions to operate. The control panel simply broadcasts system conditions on the Signaling Line Circuit (SLC) and the SOMs respond based upon the custom configuration. Each SOM provides a Class B Individual Circuit rated for 2.0 Amp @ 30 VDC. Each SOM also requires a 24 Volt power source in addition to the SLC connection.
|
VF6003: SHORT CIRCUIT ISOLATOR STANDARD FEATURES
• Can be placed at any location on SLC loop
• Checks the line for short circuit at power up.
• If the line is normal, the relay will be returned on; if a line short is detected,
...the relay remains open.
• Indication of short circuit by yellow LED
|
|
Down Loads
VF6003 Short Circuit Isolator |
|